ICM (Obsolete/Legacy Products)

ICM6200

Share:
ICM (Obsolete/Legacy Products)

ICM6200

Fan Coil Relay Control Center
The ICM6200 allows a line voltage (115 VAC) 3-speed fan to be controlled via a low voltage (24 VAC) signal or thermostat, and also provides low voltage heating/cooling valve control.
  • Ability to operate line voltage, 3-speed fan motor with low voltage controls
  • Compatible with 4-pipe, 2-pipe, heat pump, auto changeover
  • 20 VA 24 VAC power supply
  • Suitable for 1/8 HP motors
  • 1/4″” quick connect terminal
  • Mounts with standard 3″” track
  • UL Recognized
Input
  • Transformer Primary: 115 VAC, 50-60 Hz
  • Fan Inputs HI, MED, LOW: Nominal 17mA @ 24 VAC
  • Heat & Cool: 0.83A @ 24 VAC
Output
  • Transformer Secondary: 24 VAC; 20 VA
  • Relay Outputs HI, MED, LOW: 1/8 HP @ 115 VAC
    • 10A @ 240 VAC resistive max.
  • Heat & Cool Valves: 0.83A @ 24 VAC
Weight/Dimensions
  • Weight: 1.05 lb.
  • Height: 1.75″
  • Width: 5.875″
  • Length: 3″
Sell Sheet
Download
Installation Guide
Download

Honeywell: W6380B

BSR/Xactone: FC/H-2

 

Recommended Alternative: Function specific; No suggested alternative