3-Phase Plug-In Voltage Monitor
The ICM408 continuously monitors the incoming line voltage for errors. When the line voltage is appropriate, the ICM408 closes a set of N.O. contacts and lights a green LED. When the incoming voltage is outside of the user-set parameters, the N.O. contacts open and the red LED will flash a code for the particular fault present. The control will also interrogate the line voltage during the fault condition to avoid short cycling and nuisance trips
  • Reliable 3-phase protection for single side
  • Monitors for phase reversal, phase loss, unbalance % and high/low voltage
  • Bright LED indicators for ON and FAULT
  • High/low voltage cut out:
    • High voltage cut out set point: +12%
    • Low voltage cut out set point: -12%
  • Heavy duty SPDT
  • Phase reversal detection on power-up

Electrical

  • Voltage: 190-480 VAC
  • Frequency: 50/60 Hz
  • N.O./N.C. contacts: 10 amps resistive @ 250 VAC
  • Power/phase loss detection: within 100 ms
  • User selectable unbalance voltage: 2 to 8%
  • User selectable delay on make: .1 to 5 minutes
  • User selectable delay on brake: .1 to 5 minutes
Weight/Dimensions
  • Weight: 0.5 lb.
  • Height: 4″
  • Width: 2.5″
  • Length: 1.75″