ICM (Obsolete/Legacy Products)
ICM408
ICM (Obsolete/Legacy Products)
ICM408
3-Phase Plug-In Voltage Monitor
The ICM408 continuously monitors the incoming line voltage for errors. When the line voltage is appropriate, the ICM408 closes a set of N.O. contacts and lights a green LED. When the incoming voltage is outside of the user-set parameters, the N.O. contacts open and the red LED will flash a code for the particular fault present. The control will also interrogate the line voltage during the fault condition to avoid short cycling and nuisance trips- Reliable 3-phase protection for single side
- Monitors for phase reversal, phase loss, unbalance % and high/low voltage
- Bright LED indicators for ON and FAULT
- High/low voltage cut out:
- High voltage cut out set point: +12%
- Low voltage cut out set point: -12%
- Heavy duty SPDT
- Phase reversal detection on power-up
Electrical
- Voltage: 190-480 VAC
- Frequency: 50/60 Hz
- N.O./N.C. contacts: 10 amps resistive @ 250 VAC
- Power/phase loss detection: within 100 ms
- User selectable unbalance voltage: 2 to 8%
- User selectable delay on make: .1 to 5 minutes
- User selectable delay on brake: .1 to 5 minutes
Weight/Dimensions
- Weight: 0.5 lb.
- Height: 4″
- Width: 2.5″
- Length: 1.75″
Mars: 32532, 32534, 32540, 32541, 32542