Defrost Timer
 
  • Replacement for Goettl 305057 controls

Input

  • Voltage: 18-30 VAC
  • Frequency: 50-60 Hz
  • Power Consumption: 1 watt maximum

Output

  • CC, Aux. Heat, RVS
    •  Type: Relay
    • Form: SPST, normally open
    • Rating: 2 amps @ 24 VAC
  • IDF, ODF
    • Type: Relay
    • Form: SPST, normally closed
    • Rating: 10 amps @ 240 VAC

Time Delays

  • Defrost: Fixed at 10 minutes (+/- 10%)
  • Interval Between Defrost: Pin selectable (30/60/90 minutes)
Weight/Dimensions
  • Weight: 0.5 lb.
  • Width: 5.8″
  • Height: 4.25″