ICM (Obsolete/Legacy Products)
ICM2905
ICM (Obsolete/Legacy Products)
ICM2905
Reznor OEM Replacement Control
Intermittent pilot gas ignition control module for use with intermittent pilot boilers, furnaces and other heating appliances. Monitors timing, trial for ignition, flame sensing and lockout.- Intermittent pilot gas ignition control module
- For use with intermittent pilot boilers, furnaces and other heating appliances
- Microprocessor-based
- Monitors timing, trial for ignition, flame sensing and lockout
- Remote flame sensing
- 2-minute trial for ignition
- 60-minute lock out if pilot flame is not sensed in 2 minutes
- Compatible with LP or natural gas
- Damper control input
Electrical
- Control Voltage: 18-30 VAC
- Frequency: 50/60 Hz
- Operating Temperature: -40°F to 165°F, -40°C to 75°C
- Current Draw: 100 mA maximum
- Pre-Purge Delay: 0 seconds
- Trial for ignition: 2-minutes
- Lock Out Time: 60-minutes
Weight/Dimensions
- Weight: 0.45 lb.
- Height: 2″
- Width: 5.3″
- Length: 4″
Reznor: 257010
UTEC: 1097-211







































































































