ICM (Obsolete/Legacy Products)

ICM151

Share:
ICM (Obsolete/Legacy Products)

ICM151

Ideal for Stagger Starting
  • UL 873 recognition as compressor controller
  • Compressor lockout/anti-short cycle timer with random start feature
  • Safety switch lockout
  • Remote thermostat reset
  • Reduces nuisance lockouts/service calls
  • Adjustable timing
  • 18-30 VAC
Input:
  • Voltage: 18-30 VAC
  • Frequency: 50-60 Hz

Compressor Output:

  • Maximum: 1 amp
  • Minimum 40 mA
  • Inrush: 10-amps

Fault Indicator LED Connection:

  • Form: SPST, N.O., 1 Form A
  • Rating: 2 amps resistive
Time delay:
  • Lockout: Knob adjustable 6 to 600 seconds
  • Random Start: 10% of selected lockout time
Weight/Dimensions
  • Weight: 0.15 lb.
  • Height: 1.25″
  • Width: 3″
  • Length: 2″
Installation Guide
Download

York: 031-01204-000

 

Recommended Alternative: No suggested alternative